gForce Ultra IOM
88
gForce Ultra Settings:
dap4 Settings for Ultra Units
Must enter Universal Security Access password 1739 to adjust these parameters
1.
Data Aire Settings:
a.
Enter Model:
Ultra gForce
b.
Start-up Charging:
No
c.
22kW
36-45kW
70, 91, 125kW
VFD Type:
CDS-803
CDS-303
CDS-303
2.
Menu B - Setpoints:
a.
Setpoints: Temp Setpoint:
Cool Deadband:
Heat Deadband:
72F (Default)
2.0F (Default)
5.0F (Default)
b.
Humidity Setpoints: Hum Setpoint:
Hum Deadband:
50% (Default)
3% (Default)
3.
Menu G - Network Config
a.
BMS Port 1: Protocol:
Detect Heartbeat?:
Heartbeat Ok:
N/A (Default)
Yes (Default)
No (Default)
b.
pLAN Address:
1
Notice: Do not change this setting without following Zone Control instruction!
4.
Menu J Factory Settings:
a.
System Settings: Screen Flip Delay:
Temp Units:
Control:
Out Status:
Fan Type:
None (Default)
Fahrenheit (Default)
Return Air (Default)
Sys On (Default)
Plug Fan (Default)
b.
Compressor Settings:
Type:
DX Delay:
Delay Time:
Min Run Time:
Min Off Time:
Delay Btw Stages:
22kW
36-45kW
70, 91, 125kW
Sngl
Variable
Sngl
Variable
Variable
& Fixed
Initialize
5s
3m (Default)
2m (Default
60s (Default)
Minimum Speed:
Maximum Speed:
1500 RPM
5400 RPM