gForce Ultra IOM
89
dap4 Settings for Ultra Units
c.
Variable Compressor 1: Band:
Integration Time:
Derivative:
C1 Offset:
C1 Off Delay:
Minimum Speed:
Maximum Speed:
18.0F (Default)
1000s (Default)
0 (Default)
2.0F (Default)
60s (Default)
1500 RPM
6000 RPM
NOTE: When Analog Output Config: Optional Output #2 is changed, these speeds must be
changed proportionally. Example: Max Speed = (6000 RPM / 10) x 9.0 VDC = 5400 RPM
d.
Variable Compressor 2:
Delay Modulation:
C2 Offset:
C1 Boost Time:
C2 On Delay:
C2 Off Delay:
Oil Boost Delay:
22kW
36-45kW
70, 91, 125kW
Not required for a GUXX-
022XX, GUXX-036 or
GUXX-045XX models
Ignore any parameters in
this menu, they do not
apply.
60s (Default)
1.0F (Default)
60s (Default)
60s (Default)
60s (Default)
90s (Default)
e.
Variable Compressor 3:
22kW
36-45kW
70, 91, 125kW
Suction Pr:
Cut Out SP:
Differential:
Delay C1 Start:
Maximum PD Time:
SH PD Cut-In:
Not required for a GUXX-
022XX, GUXX-036 or
GUXX-045XX models
Ignore any parameters in
this menu, they do not
apply.
XX PSI
(Reading, not a
setting)
80 PSI (Default)
40PSI (Default)
5s (Default)
60S (Default)
30.0 (Default)
f.
Options Installed:
22kW
36-45kW
70, 91, 125kW
Electronic Valve:
Expansion Module:
Power Meter:
AC Pwr Loss Cap:
Enable Pump Down:
Rack Temp:
Sngl
Sngl
Dual
pCOe (Default)
No (Default)
No (Default)
Yes (Air-cooled systems)
No (Water/Glycol-cooled systems)
None (Default)
g.
Reheat Settings: Reheat Stages:
Enable Rotation:
Lead Reheat:
Dly After CL:
Enable SCR Y4:
Band:
None See Job Instructions
Yes (Default)
First (Default)
10 min (Default)
No (Default)
1F (Appears if SCR is enabled)