dap4 Settings for Ultra Units
Water Valve Settings: Water Valve:
E-Saver Assist:
Wtr Vlv Action:
Wtr Vlv Voltage:
E/S Startup Time:
E/S Lockout Time:
Switch to DX:
None (Default)
Aux Chill Wtr or Engy Svg Cool
Direct (Default)
0-10
0s (Default)
5m (Default)
0 Hrs (Default)
CAUTION: NEVER SELECT Chill Wtr Cool or Chill Wtr Reg on Ultra model; otherwise
compressor(s) will not operate.
Humidity Settings:
Control:
Humidify:
Auto-Flush:
Dsat Cyc:
Hum Anticipation:
See Job Instructions
Relative Hum (Default)
Compu Non-Mod
Not used (Default),
Not used (Default)
Off (Default)
Humidity Settings 2:
Dehum Mode:
Fan Speed Assist:
Reduce Speed:
See Job Instructions
2C In Limit
Off (Default)
20% (Default) Only appears if fan speed
assist is selected to yes
Rack Settings:
Temp Sensors Used:
Optional RackSense module required
0 (Default)
Unit Identification: Model:
Serial Number:
Job Number:
GUXX-022XX-XX
20XX-XXXX-X
4XXXX
Fan Settings: CW mode:
CW speed;
Display Airflow:
Aire-Seal Damper:
DX Mode:
DX Speed:
Const Speed (Default)
85% (Default)
No (Default)
No (Default)
Mod to Comp
XX% (See Job Instructions)
Fan Range Setting – This screen will display if Mod to Comp, Mod to Rack, BMS Flow, Const
Flow, Air Pressure, or BMS Speed is selected
Modulate Min:
Modulate Max:
40% (Default)
XX% (See Job Instructions)
Options Installed 2: Condenser Fans:
Evaporator Fans:
None (Default)
None (Default)
Diff Air Pressure - This screen will display if Display Airflow is selected
Set Point:
Band:
Integration Time:
Fan Speed:
1.000” Wtr (Default)
5.000” Wtr (Default)
50s (Default)
0% (Default)
Fan Air Flow - This screen will display if Display Airflow is selected