dap4 Settings for Ultra Units
Comp Envelope Alarm: Envelope Protect:
Start-Up Delay:
Run Outside Delay:
Max Number Alarms:
Yes (Default) (Air-cooled Only)
100s (Default)
1s (Default)
3 (Default) In 1 (Default) day, to Lock-out
Pump-Down Alarm: Failed PD Alarm:
Yes (Default)
(Pump-Down feature will still operate)
Alarm Inputs:
Custom Alarm Messages Alarm #1 (DI-13):
Custom Alarm Messages Alarm #2 (DI-14):
See Tag Inside Door (Default)
See Tag Inside Door (Default)
Alarm Inputs:
Custom Alarm Messages Alarm #3 (DI-15):
Custom Alarm Messages Alarm #4 (DI-16):
Compressor VFD Alarm (for Dual VS Comp 2)
Compressor VFD Alarm (for Sngl VS Comp 1)
Alm Output Function 1 to 9:
All #1 = Y. All #2, #3 and #4 = N
Digital Input: C1 Hi Pressure Sw Channel:
Action:
Delay:
Status:
ID1 (Default)
Open (Default)
5s (Default)
Open Info Only Based on Sw State
Digital Input: C1 Low Pressure Sw Channel:
Action:
Delay:
Status:
ID2 (Default)
Open (Default)
5s (Default)
Open Info Only Based on Sw State
Digital Input: C2 Hi Pressure Sw Channel:
Action:
Delay:
Status:
ID3 (Default)
Open (Default)
5s (Default)
Open Info Only Based on Sw State
Digital Input: C2 Low Pressure Sw Channel:
Action:
Delay:
Status:
ID4 (Default)
Open (Default)
5s (Default)
Open Info Only Based on Sw State
Digital Input: Air Flow Switch Channel:
Action:
Delay:
Status:
ID5 (Default)
Closed (Default)
5s (Default)
Open Info Only Based on Sw State
Digital Input: Water Flow Switch Channel:
Action:
Delay:
Status:
ID6 (Default)
Closed (Default)
5s (Default)
Open Info Only Based on Sw State
Digital Input: Smoke Detector Sw Channel:
Action:
Delay:
Status:
ID7 (Default)
Closed (Default)
5s (Default)
Open Info Only Based on Sw State