dap4 Settings for Ultra Units
Digital Input: Manual Override Channel:
Action:
Delay:
Status:
ID18 (Default)
Closed (Default)
5s (Default)
Open Info Only Based on Sw State
Analog Input: Humidity Sensor: Enable:
Channel:
Normal:
Minimum:
Maximum:
Offset:
Value:
On (Default)
U01 (Default)
4-20mA (Default)
0.0 (Default)
100.0 (Default)
0.0 (Default)
000.0 (Reading, not a setting)
Analog Input: Return Air Sensor: Enable:
Channel:
High Res.:
Offset:
Value:
On (Default)
U04 (Default)
NTC (Default)
0.0 (Default)
000.0 (Reading, not a setting)
Analog Input: Static Air Pressure: Enable:
Channel:
Normal:
Min 1/1000” H2O:
Max 1/1000” H2O:
Offset:
Air Press:
Off (Default)
U07 (Default)
0-10VDC (Default)
0 (Default)
5000 (Default)
000 (Default)
0.000” Wtr (Reading, not a setting)
Analog Input: Discharge Air Pressure: Enable:
Channel:
High Res.:
Offset:
Value:
On (Default)
U09 (Default)
NTC (Default)
0.0F (Default)
0.000F (Reading, not a setting)
Analog Input: Chilled Water Sensor: Enable:
Channel:
High Res.:
Offset:
Value:
Off (Default)
U10 (Default)
NTC (Default)
0.0F (Default)
0.000F (Reading, not a setting)
Analog Input: Outside Air Temp: Enable:
Channel:
Normal:
Offset:
Value:
Off (Default)
U05 (Default)
NTC (Default)
0.0F (Default)
0.000F (Reading, not a setting)
Optional Sensor #1: Choose Name: Enable:
Channel:
Normal:
Offset:
Value:
Off (Default)
U02 (Default)
NTC (Default)
0.0F (Default)
0.0F (Reading, not a setting)