10-2014 gForce User Manual ● 85
Move the cursor to the title block by pressing the ENTER key stepping through all the
inputs. To return to the main Menu press the ESC key or to view the following screen
press the DOWN key.
The following screen will be displayed (values are for reference only):
Temp Sensors Used: Up to 32 rack temperature sensors may be used. The default is
None. The rack temperature can be used to control the fan speed when the fan control
is set to “Mod to Rack”. Otherwise, it is only for reference.
Group Used: This is the number of sensor groups. The default value is None. Rack
sensors can be arranged in up to 16 individual groups. The temperature of each group
is the average of its associated sensors
Exclude T Band: If any rack temperature sensor is higher or lower than the rack
temperature this amount, it will be excluded from the rack temperature calculation.
Refresh Rate: This setting determines how often the highest of the rack temperature
sensors or groups of sensors is calculated. The default value is every 5 mins.
Offset Setpoint: Default is No. This feature will automatically offset the temperature
setpoint -0.1F every 60 seconds if the fan is running at its maximum speed yet the
rack inlet temperature is not satisfied. The setpoint will not be offset below the
discharge temperature limit which is default to 45F. Note: This feature requires an
optional discharge air sensor.