92 ● gForce Ultra User Manual 10-2014
The following screen will be displayed (values are for reference only):
Press the ENTER key to move through the alarm/message inputs.
Press the UP or DOWN keys to change the alarm/message.
The following selections are available:
Hi Humidity Alarm:
Yes or No (factory setting is Yes)
Set Point:
35 90% RH (factory setting is 60%)
Lo Humidity Alarm:
Yes or No (factory setting is Yes)
Set Point:
10 65% RH (factory setting is 40%)
NOTE:
If No is selected for the Hi or Low Humidity, the setpoint will not be
displayed. Once the selections have been made, with the cursor on the title
line, Press the DOWN key to advance to the next screen.