EasyManuals Logo

Dectron DRY-O-TRON Supervisaire DSV 020 User Manual

Default Icon
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
T.A.B. Prepare to Run Blower(s)
Data subject to change without notice.
180
DECTRON
Confirm that all air filters are clean and in place.
Taking care not to overflow the drain pan, pour a
bucket of water into the evaporator drain pan. Be
sure the condensate drain system works. Look for
leaks in the condensate-drain piping.
If the evaporator-bypass damper is manually
operated, be sure it is completely open.
CLOSE AND LATCH ALL AIR-
COMPARTMENT DOORS AND
ACCESS PANELS.
NOTE: The control-enclosure door is not an air-
compartment door.
When the blower starts (instructions on subsequent
page), the strong suction on the air compartment
could cause an open door to close suddenly.
Be sure to close and secure them before
starting
the blower.
Air Compartment Doors
Control Enclosure Door
(Air compartment doors on the
other side are not shown.)
Sample Only
Actual layout
may vary.
Sample
Actual layout
may vary.
Risk of contact with moving parts. Can cause injury or death.
This product contains rotating parts and V-belt drives. Some installation, service, and
maintenance procedures could expose personnel to the risk of injury or death from
contact with these parts.
Using only approved devices (e.g. locking safety switch), disconnect, lockout, and
tagout all sources of electrical energy before working inside the unit cabinet. Allow
adequate time for rotating parts to stop. Follow all applicable safety regulations.
WARNING
T.A.B.
5.12

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 020 and is the answer not in the manual?