Stop/Reset Mode
This button places the module into its Stop/Reset Mode . This clears any alarm
conditions for which the triggering criteria have been removed. If the engine is
running and the module is put into Stop mode, the module automatically instructs
the generator to unload (Close Gen becomes inactive (if used)). The fuel supply
de-energises and the engine comes to a standstill. Should any form of remote start
signal be present while operating in this mode, a start does not occur.
Auto Mode
This button places the module into its Auto Mode . This mode allows the
module to control the function of the generator automatically. The module monitors
the Remote Start input and battery charge status and once a start request is made,
the set is automatically started and placed on load (Close Gen becomes active (if
used)).
Upon removal of the starting signal, the module removes the load from the
generator and shut the set down observing the Stop Delay timer and Cooling Down
timer as necessary (Close Gen deactivates (if used)). The module then awaits the
next start event. For further details, see the more detailed section of Operation
elsewhere in this manual.
Manual/Start Mode
This button starts the engine and runs it on load. For further details, see the more
detailed section of Operation elsewhere in this manual.
Menu Navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, see the more detailed section of Operation elsewhere in this
manual.