5.3.3 ENGINE RUNNING
NOTE: The Close Gen remain inactive until the Oil Pressure has risen. This prevents
excessive wear on the engine.
Once the engine is running and all starting timers have expired, the animated Engine Running icon
is displayed.
Once the generator is available, it is then placed on load (Close Gen output becomes active (if used))
if requested.
If all start requests are removed, the Stopping Sequence begins.
5.3.4 STOPPING SEQUENCE
The Return Delay timer operates to ensure that the starting request has been permanently removed
and isn’t just a short term removal. If another start request be made during the Cooling Down timer,
the set returns on load.
If there are no starting requests at the end of the Return Delay timer, the load is removed from the
generator (Close Gen output deactivates (if used)) and the Cooling Down timer is initiated.
The Cooling Down timer allows the set to run off load and cool sufficiently before being stopped. This
is particularly important where turbo chargers are fitted to the engine.
After the Cooling Down timer has expired, the set is stopped.