EasyManua.ls Logo

DEEP SEA ELECTRONICS DSEGenset DSE3110 - INPUT SOURCES; ALARM ACTION; DIGITAL INPUT ALARM ARMING; DIGITAL INPUT POLARITY

DEEP SEA ELECTRONICS DSEGenset DSE3110
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Front Panel Configuration
Page 49 of 56
057-086 ISSUE: 6
6.3.2 INPUT SOURCES
Input Source
0
User Configured
1
RESERVED Alarm Mute
2
RESERVED Alarm Reset
3
Alternative Configuration
4
Coolant Temperature Switch
5
Emergency Stop
6
External Panel Lock
7
RESERVED Generator Closed Auxiliary
8
RESERVED Lamp Test
9
Low Fuel Level Switch
10
Oil Pressure Switch
11
Remote Start Off Load
12
Remote Start On Load
13
Smoke Limiting
6.3.3 AC TOPOLOGY
AC System
Index
Type
Instrumentation
0
Single Phase 2 Wire
L-N
1
2 Phase 3 Wire (L1 to L2 or L1 to L3)
L-N x 2
2
3 Phase 4 Wire
L-N x
3
3
3 Phase 3 Wire
L-N
4
3 Phase 4 Wire (Delta)
L-N x 2
6.3.4 ALARM ACTION
Alarm Action
Index
Action
0
Electrical Trip
1
Shutdown
2
Warning
6.3.5 DIGITAL INPUT ALARM ARMING
Digital Input Alarm Arming
Index
Arming
0
Always
1
From Safety On
2
From Starting
3
Never
6.3.6 DIGITAL INPUT POLARITY
Digital Input Polarity
Index
Polarity
0
Close to Activate
1
Open to Activate

Table of Contents