Plug #8, AC current inputs
CT on terminals 59-60: Not available for AGC 21x/22x.
Term. Function Technical data Description
53 L1 s1 1 or 5 A AC Current phase L1
54 L1 s2
55 L2 s1 1 or 5 A AC Current phase L2
56 L2 s2
57 L3 s1 1 or 5 A AC Current phase L3
58 L3 s2
59 L4 s1 1 or 5 A AC Configurable: Differential current, neutral current, ground current or
mains current
60 L4 s2
Plug #9, generator AC voltage inputs
Term. Function Technical data Description
61 L 1 100 to 690 V AC Generator line 1
62 Not used
63 L 2 100 to 690 V AC Generator line 2
64 Not used
65 L 3 100 to 690 V AC Generator line 3
66 Not used
67 N Generator neutral
All AC voltage inputs are galvanically separated from the rest of the unit. Voltages are indica-
ted in phase-phase values.