6. Technical information
6.1 Technical specifications
Accuracy Class 1.0
-40 to 15 to 30 to 70 °C
Temperature coefficient:
+/-0.2 % of full scale per 10 °C
Short circuit:
5 % of 3.5*nominal current
Earth current:
2 % of 1 A or 5 A
To IEC/EN 60688
Operating tem-
perature
-25 to 70 °C (-13 to 158 °F)
UL/cUL Listed: Max. ambient temp. 50 °C/122 °F
With option L2: -40 to 70 °C (-40 to 158 °F)
Storage temper-
ature
-40 to 70 °C (-40 to 158 °F)
Climate 97 % RH to IEC 60068-2-30
Operating alti-
tude
Up to 3000 m above sea level
Measuring volt-
age
100 to 690 V AC (+20 %)
UL/cUL Listed: 100 to 600 V AC
Phase to phase
Load: 1.5 MΩ
Frequency 30 to 70 Hz
Measuring cur-
rent
1 A or 5 A AC from current transformer
Consumption max.: 0.3 VA/phase
UL/cUL Listed: Use listed or R/C (XODW2.8) current transformers
Current over-
load
The unit has been tested with the following currents:
I
n
20 A: 60 s
I
n
100 A: 10 s
I
n
300 A: 1 s
AGC 200 installation instructions
4189340610 UK
Technical information
DEIF A/S Page 62 of 67