Magnetic pick-
up input
Voltage: 2 to 70 V peak
Frequency: 10 to 10000 Hz
Resistance: 250 to 3000 Ω
Aux. supply 6 to 36 V DC continuously
UL/cUL Listed: 9 to 32.5 V DC
0 V DC for 50 ms when coming from at least 12 V DC (cranking dropout)
Reverse protection: -36 V continuously
Battery voltage measurement accuracy:
±0.8 V within 8 to 30 V DC at -25 °C to 70 °C
±0.5 V within 8 to 30 V DC at 20 °C
Max. 25 W consumption
With option L2 -40 °C (-40 °F)
Max. 45 W consumption
The aux. supply inputs are to be protected by a 12 A slow-blow fuse
Passive binary
input voltage
Bi-directional optocoupler
ON: 8 to 36 V DC
<2 V: OFF
Impedance: 4.7 kΩ
Emergency
stop input volt-
age
ON: +8 to 36 V DC (term. 25)
<2 V: OFF
Impedance: 4.7 kΩ
Multi-functional
inputs
Current input: 0(4) to 20 mA
From active transmitter: 0 to 20 mA, +/-1 %
Impedance: 50 Ω
Binary input: Dry contact inputs 3 V DC internal supply, with cable supervision
Max. resistance for ON detection: 100 Ω
Pt100: -40 to 250 °C (-40 to 482 °F) +/-1 %
To IEC/EN 60751
RMI: 0 to 2500 Ω, +/-1 %
AGC 200 installation instructions
4189340610 UK
Technical information
DEIF A/S Page 63 of 67