Setup of a controller with engine communication and AVR option
Nominal
freq.
No
Yes
End
Yes
Start
Nominal
voltage
Adjust 2551
GOV offset
Adjust AVR
voltage
No
No
2781
Select EIC for
GOV
Start DG in
MAN mode
2782
Select relay for
AVR
2723
Select incr.
relay for AVR
2724
Select decr.
relay for AVR
2740
Adjust timer
Copy 2510
sett. to 2530,
2540, 2040
2510 adjust Kp,
Ti and Td
2720 set AVR
ON time to
minimum
Switch to Semi
Auto mode
2690 adjust Kp
Copy 2690
sett. to 2700,
2710
For further information, please refer to the General Guidelines for Commissioning.
AGC 200 quick start guide 4189340608 UK Display push-buttons and LEDs
DEIF A/S Page 20 of 21