6. Engine functions
6.1 Engine sequences
The engine start and stop sequences are started automatically if AUTO mode is selected. In manual mode, the operator has
to initiate the sequences.
6.2 Engine start functions
6.2.1 Start sequence
The following drawing shows the start sequence of the genset.
Configure the run coil timer to activate the fuel relay output and the idle mode output before pre-heat is completed.
Timers
Timers > Cranking
Parameter
Range Default
Crank Hold Time 1 to 255 s 5 s
Crank Rest Time 2 to 60 s 5 s
Manual Start Delay 0 to 300s 3 s
Auto Start Delay 0 to 43200 s 3 s