Level 2 Range
(BATTERY MON) Disable
Low Voltage Threshold
(LOW BATT THRESHOLD)
12.0 to 60.0 V
Battery Monitoring Delay
(LOW BATT MON DELAY)
5 to 300 s
Genset Run Duration
(GEN RUN DURATION)
1 to 720 min.
Table 6.5 Cyclic Mode (CYCLIC CONFIG)
Level 2 Range
Cyclic Mode
(CYCLIC MODE)
Enable
Disable
Genset Off Time
(GEN OFF DURATION)
1 to 720 min.
Genset On Time
(GEN ON DURATION)
1 to 720 min.
Table 6.6 Auto Exercise – Event 1 (AUTO EXERCISE – 1)
Level 2 Range
Auto Exercise
(EVENT 1)
Enable
Disable
Event Occurrence
(EVENT OCCURENCE)
Daily
Weekly
Monthly
Event Day
(EVENT DAY)
Daily: Runs every day
Weekly: Sunday to Saturday
Monthly: 1 to 28
Start Time
(START TIME)
00:00 to 23:59 hour
Duration
(GEN ON DURATION)
00 hr 01 min. to 99 hr 59 min.
Load Transfer
(LOAD TRANSFER)
Enable
Disable
Table 6.7 Auto Exercise – Event 2 (AUTO EXERCISE – 2)
Level 2 Range
Auto Exercise
(EVENT 2)
Enable
Disable
Event Occurrence
(EVENT OCCURENCE)
Daily
Weekly
Monthly
Event Day
(EVENT DAY)
Daily: Runs every day
Weekly: Sunday to Saturday
Monthly: 1 to 28
Start Time
(START TIME)
00:00 to 23:59 hour
USER MANUAL 4189341227A UK Page 24 of 86