Level 2 Range
(Digital) Polarity
((DIG) POLARITY)
Close to Activate
Open to Activate
(Digital) Action
((DIG) ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
(Digital) Activation
((DIG) ACTIVATION)
Never
From Engine Start
From Monitoring On
Always
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
1 to 180 s
(LOP) Circuit Fault Action
(OPEN CKT ALARM)
None
Notification
Warning
Electrical Trip
Shutdown
(LOP) Lube Oil Pressure Calibration Table
Resistance: 0 to 1000 Ω
Pressure: 0.0 to 10.0 Bar
Table 6.11 Analogue Input 2 (FUEL LVL / DIG K)
Level 2 Range
Use Input As
(SENSOR SELECTION)
Not used
Digital Input K
Fuel Level Sensor
(Digital) Source
((DIG) SOURCE)
See Digital input source selection in this document
Name
(NAME)
Auxiliary Input K
(Digital) Polarity
((DIG) POLARITY)
Close to Activate
Open to Activate
(Digital) Action
((DIG) ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
(Digital) Activation
((DIG) ACTIVATION)
Never
From Engine Start
From Monitoring On
Always
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
1 to 180 s
(FLS) Low Fuel Level Shutdown
(SHUTDOWN)
Enable
Disable
(FLS) Shutdown Threshold
(SHUTDOWN THRESHOLD)
0 to 78 %
(FLS) Low Fuel Level Notification
(NOTIFICATION)
Enable
Disable
USER MANUAL 4189341227A UK Page 26 of 86