Level 2 Range
(FLS) Notification Threshold
(NOTIFICATION THRESHOLD)
2 to 80 %
(FLS) Fuel Tank Capacity
(FUEL TANK SIZE)
2 to 1000 litre
(FLS) Fuel Theft Warning
(FUEL THEFT ALARM)
Enable
Disable
(FLS) Fuel Theft Alarm Threshold
(FUEL LVL THRESH)
1 to 100 % per hour
(FLS) Circuit Fault Action
(OPEN CKT ALARM)
None
Notification
Warning
Electrical Trip
Shutdown
(FLS) Fuel Sensor Reference
(FUEL LVL REF)
Battery Negative
Engine Body
(FLS) Fuel Level Sensor Calibration Table
Resistance: 0 to 5000 Ω
Fuel level: 0 to 100 %
Table 6.12 Analogue Input 3 (ENG TEMP / DIG L)
Level 2 Range
Use Input As
(SENSOR SELECTION)
Not used
Digital Input L
Engine Coolant Temperature Sensor
(Digital) Source
((DIG) SOURCE)
See Digital input source selection in this document
Name
(NAME)
Auxiliary Input L
(Digital) Polarity
((DIG) POLARITY)
Close to Activate
Open to Activate
(Digital) Action
((DIG) ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
(Digital) Activation
((DIG) ACTIVATION)
Never
From Engine Start
From Monitoring On
Always
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
1 to 180 s
(ETS) Circuit Fault Action
(OPEN CKT ALARM)
None
Notification
Warning
Electrical Trip
Shutdown
(ETS) Engine Temperature Sensor Calibration Table
Resistance: 0 to 5000 Ω
Temperature: -25 to 300 °C
USER MANUAL 4189341227A UK Page 27 of 86