Table 6.14 S2 Sensor (AUX S2 RES / DIG N)
Level 2 Range
Use Input As
(SENSOR SELECTION)
Not used
Digital Input N
S2 Sensor
(Digital) Source
((DIG) SOURCE)
See Digital input source selection in this document
Name
(NAME)
Auxiliary Input N
(Digital) Polarity
((DIG) POLARITY)
Close to Activate
Open to Activate
(Digital) Action
((DIG) ACTION)
None
Notification
Warning
Electrical Trip
Shutdown
(Digital) Activation
((DIG) ACTIVATION)
Never
From Engine Start
From Monitoring On
Always
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
1 to 180 s
(S2) Shutdown
(SHUTDOWN)
Enable
Disable
(S2) Shutdown Threshold
(SHUTDOWN THRESHOLD)
0.0 to 1000.0
(S2) Warning
(WARNING)
Enable
Disable
(S2) Warning Threshold
(WARNING THRESHOLD)
0.0 to 1000.0
(S2) Threshold Type
(THRESHOLD TYPE)
Greater Than Threshold
Less Than Threshold
(S2) Circuit Fault Action
(OPEN CKT ALARM)
None
Notification
Warning
Electrical Trip
Shutdown
(S2) Calibration Table
Resistance: 0 to 5000 Ω
Value: 0 to 1000
Table 6.15 S3 Sensor (AUX S3 CURR / DIG O)
Level 2 Range
Use Input As
(SENSOR SELECTION)
Not used
Digital Input O
4 to 20 mA Sensor
0 to 5 V Sensor
(Digital) Source
((DIG) SOURCE)
See Digital input source selection in this document
Name Auxiliary Input O
USER MANUAL 4189341227A UK Page 29 of 86