Register
address
Parameter Scale Factor
Unit/
Interpretation
Bits/Sign
79
Alarm 8
Auxiliary input A -- -- 13/16-16/16
Auxiliary input B -- -- 9/16-12/16
Auxiliary input C -- -- 5/16-8/16
Auxiliary input D -- -- 1/16-4/16
80
Alarm 9
Auxiliary input E -- -- 13/16-16/16
Auxiliary input F -- -- 9/16-12/16
Auxiliary input G -- -- 5/16-8/16
Auxiliary input H -- -- 1/16-4/16
81
Alarm 10
Auxiliary input I -- -- 13/16-16/16
Auxiliary input J -- -- 9/16-12/16
Auxiliary input K -- -- 5/16-8/16
Auxiliary input L -- -- 1/16-4/16
82
Alarm 11
Auxiliary input M -- -- 13/16-16/16
Auxiliary input N -- -- 9/16-12/16
Auxiliary input O -- -- 5/16-8/16
Auxiliary input P -- -- 1/16-4/16
83
Alarm 12
Gen L1 phase low volt -- -- 13/16-16/16
Gen L1 phase high volt -- -- 9/16-12/16
Gen L2 phase low volt -- -- 5/16-8/16
Gen L2 phase high volt -- -- 1/16-4/16
84
Alarm 13
Gen L3 phase low volt -- -- 13/16-16/16
Gen L3 phase high volt -- -- 9/16-12/16
DG phase rotation -- -- 5/16-8/16
Mains phase rotation -- -- 1/16-4/16
85
Alarm 14 --
Extended overload trip -- -- 13/16-16/16
V belt broken -- -- 9/16-12/16
Open fuel level -- -- 5/16-8/16
High oil pressure detected -- -- 1/16-4/16
USER MANUAL 4189341227A UK Page 64 of 86