EasyManua.ls Logo

Deif SGC 420 - Page 76

Deif SGC 420
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communication structure, page 20
Register offset Value Scale factor Unit Bits/Sign
55 Charge alternator voltage 1 V Unsigned
56 Battery voltage 1 V Unsigned
57 Engine speed 1 RPM Unsigned
Communication structure, page 21
Register offset Value Scale factor Unit Bits/Sign
58 No of starts 1 - Unsigned
59 No of trips 1 - Unsigned
60 Eng run hrs 1 hrs Unsigned
Communication structure, page 22
Register offset
Value Scale factor Unit Bits/Sign
61 Eng run min 1 min Unsigned
62 Mains run hrs 1 hrs Unsigned
63 Mains run min 1 min Unsigned
Communication structure, page 23
Register offset
Value Scale factor Unit Bits/Sign
64
Alarm 1
Low oil pressure -
E-0001/0001
W-0010/0010
S-0011/0011
3/16-16/16
High coolant temperature -
E-0001/0001
W-0010/0010
S-0011/0011
9/16-12/16
Radiator water level/low fuel level -
E-0001/0001
N-0101/0101S-0
011/0011
5/16-8/16
Water level switch -
E-0001/0001
N-0101/0101
W-0010/0010
E-0100/0100
S-0011/0011
1/16-4/16
65
Alarm 2
Under speed -
E-0001/0001
S-0011/0011
13/16-16/16
Over speed -
E-0001/0001
S-0011/0011
9/16-12/16
Fail to start -
E-0001/0001
S-0011/0011
5/16-8/16
Fail to stop -
E-0001/0001
S-0011/0011
1/16-4/16
USER MANUAL 4189341227A UK Page 76 of 86