Particulate contamination Specications
NOTE
: This condition applies to data center and non-data center
environments.
Table 33. Gaseous contamination specica
tions
Gaseous contamination Specications
Copper coupon corrosion rate <300 Å/month per Class G1 as de
ned by ANSI/ISA71.04-2013.
Silver coupon corrosion rate <200 Å/month as dened by ANSI/ISA71.04-2013.
NOTE
: Maximum corrosive contaminant levels measured at ≤50% relative humidity.