AC power specifications
Table 7 Input power requirements - Single-phase, North American, International, Australian
Specification North American 3-wire
connection
(2 L & 1 G)
a
International and
Australian 3-wire
connection
(1 L & 1 N & 1 G)
a
Input nominal voltage 200–240 VAC ± 10% L- L
nom
220–240 VAC ± 10% L- N
nom
Frequency 50–60 Hz 50–60 Hz
Circuit breakers 30 A 32 A
Power zones Two Two
Minimum power requirements
at customer site
l
PowerMax 2000: Up to two 30 A or 32 A single-phase
drops per zone.
l
PowerMax 8000: Up to three 30 A or 32 A single-phase
drops per zone.
l
Two power zones require 6 drops, each drop rated for 30
A or 32 A. (Maximum PowerMax 8000 configuration.)
l
PDU A and PDU B require three separate single-phase 30
A or 32 A drops for each PDU.
a.
L = line or phase, N = neutral, G = ground
Best Practices Guide for AC Power Connections
AC power specifications 27