• Use or create no more than one floor tile cutout that is no more than 8 in. (20 cm) wide by 6 in. (15 cm) deep in each 24 x 24 in. (61 x
61 cm) floor tile.
• Ensure that the weight of any other objects in the data center does not compromise the structural integrity of the raised floor or the
sub-floor (non-raised floor) of the data center.
Physical space and weight
The following table provides the physical space, maximum weights, and clearance for service.
PowerMax 2000
Table 15. Space and weight requirements, PowerMax 2000
Bay configurations
a
Height
(in/cm)
b
Width
(in/cm)
Depth
c
(in/cm)
Weight
(max lbs/kg)
1 system, 1 PowerBrick 75/190 24/61 42/106.7 620/281
1 system, 2 PowerBricks, or
2 systems, 1 PowerBrick each
75/190 24/61 42/106.7 950/430.9
2 systems, 2 PowerBricks in
one system, 1 PowerBrick in
other
75/190 24/61 42/106.7 1280/580
2 systems, 2 PowerBricks
each system
75/190 24/61 42/106.7 1610/730
a.
Clearance for service/airflow is the front at 42 in (106.7 cm) front and the rear at 30 in (76.2 cm).
b.
An additional 18 in (45.7 cm) is recommended for ceiling/top clearance.
c.
Includes rear door.
PowerMax 8000
Table 16. Space and weight requirements, PowerMax 8000
Bay
configurations
a
Number of
PowerBricks
Height
b
(in/cm)
Width
c
(in/cm)
Depth
d
(in/cm)
Weight
(max lbs/kg)
System Bay 1 1 75/190 24/61 47/119 805/365
2 75/190 24/61 47/119 1104/501
3 75/190 24/61 47/119 1418/643
4 75/190 24/61 47/119 1667/756
System Bay 2 1 75/190 24/61 47/119 663/301
2 75/190 24/61 47/119 962/436
3 75/190 24/61 47/119 1276/579
4 75/190 24/61 47/119 1525/692
a.
Clearance for service/airflow is the front at 42 in (106.7 cm) front and the rear at 30 in (76.2 cm).
b.
An additional 18 in (45.7 cm) is recommended for ceiling/top clearance.
c.
Measurement includes .25 in. (0.6 cm) gap between bays.
d.
Includes front and rear doors.
22 Physical Weight and Space