Grounding Racks
Supplemental rack grounding is not required for single bay configurations. Chassis to chassis grounding is required for systems with
multiple bays.
Topics:
Grounding requirements
Grounding a single bay
Chassis to chassis grounding
Grounding requirements
The following table summarizes rack grounding requirements for PowerMax systems.
Number of racks in system Grounding required? Reference
1 No Grounding a single bay on page 44
2+ Yes Chassis to chassis grounding on page 45
Grounding a single bay
Equipment correctly installed within the cabinet is grounded through the AC power cables and connectors. In general, supplemental
grounding is not required for a single bay.
If your site requires external grounding (for example, to a common grounding network beneath the site floor), you can use the grounding
lugs provided on each of the cabinet’s bottom supports.
9
44 Grounding Racks