Figure 15. Customer input power outlet, three-phase
Single-phase power
In a PowerMax 8000 system on single-phase power, line cords are required in outlets P1, P3 and P5 depending on the number of
PowerBricks in the system. Refer to Table 29. PowerMax 8000 line cord configurations, single-phase on page 42 for the location of the
line cords required for each PowerBrick.
Two jumpers, PN 038-004-186, are pre-installed at the factory and should not be removed. Jumpers are located in the following locations:
J1<>P2
J5<>P6
Each line cord energizes the circuit breakers and corresponding PDU outlets as follows:
Table 29. PowerMax 8000 line cord configurations, single-phase
PowerBrick Components Line cord location Circuit breakers PDU outlets
PowerBrick 4/8 DAE 6 No additional line
cords required
-- --
SPS 4A/4B
PowerBrick 3/7 DAE 5 P5 9-12 25-37
DAE 4
SPS 3A/3B
PowerBrick 2/6 DAE 3 P3 5-6 13-18
SPS 2A/2B
PowerBrick 1/5 DAE 2 P1 1-4 1-12
DAE 1
MIBE A/B
(PowerBrick 1 ONLY)
Ethernet switch A/B
(PowerBrick 1 ONLY)
SPS 1A/1B
NOTE: Circuit breakers 7-8 and PDU outlets 19-24 are not energized on a PowerMax 8000 system with single-phase
power.
42 Power Cabling, Cords and Connectors