Figure 82. FS25 three phase WYE power cabling
5. For DS60 shelves, connect each power supply to redundant power sources in the rack.
Figure 83. DS60 single phase power cabling
Figure 84. DS60 three phase delta power cabling
Figure 85. DS60 three phase WYE power cabling
6. Repeat the preceding steps for each shelf in the rack.
Connecting controller power cables and powering on
Prerequisites
Connect the power cables to power on the disk shelves before powering on the controller.
Steps
1. Verify the jumpers at the bottom of each PDU are set correctly. From the back of the rack, Zone B is on the left-hand and
Zone A is on the right-hand side. The following images show the jumpers for each type of power connection
● Single phase power
Connect Cables and Power On
71