Remove filler panels
The front space into which you will install the shelf is usually covered by a filler panel. If one or
more filler panels cover the space where you want to install the shelf, use this procedure to
remove each panel.
Procedure
1. On the filler panel, slide the left and right securing tabs to the open position (towards the
center of the panel).
2. Remove the filler panel from the cabinet.
Recommended rack locations for the system
Ensure that you install the system controllers and disk shelves in the appropriate rack locations.
Note:
The following recommended rack locations support the cabling described in this
document. Installing in other locations might require different cable lengths.
The following table lists the recommended locations for installing the system in the rack.
Table 2
DD9900 system racking locations
Component Configuration Rack location
Controller location with
ES40 shelves
Single node or high-availability (HA)
primary node
U13-U15
HA standby node U17-U19
FS25 location with ES40
shelves
Single node and HA U39-40
ES40 locations Single node or HA
l
Rack 1 (10 shelves):
U01-U12, U21-U38
l
Rack 2 (10 shelves):
U01-U30
Controller location with
DS60 shelves
Single node or HA primary node U12-U14
HA standby node U16-18
Install the System in the Rack
20 Dell EMC PowerProtect DD9900 System Installation Guide