In Linux, the le is located at: /opt/dell/ServerHardwareManager/bin.
2 Under the [SHMSYSTEM] section of the le, add or edit the entry 3060eLEDControl.
To turn the behavior on: 3060eLEDControl=ON.
To turn the behavior o: 3060eLEDControl=OFF.
NOTE: If the 3060eLEDControl item is missing or blank, the behavior by default is
o.
3 Save the le.
4 Restart the monitoring service.
If the LED control behavior is turned on, the following LED control will occur:
1 If a drive is reporting a predicted failure state:
a The drive slot LED will be set to the Identify state.
b The enclosure LED will be set to the Failure state.
2 If a drive is determined to be in a failed state:
a The drive slot LED will be set to the Failure state.
b The enclosure LED will be set to the Failure state.
Monitoring 45