Figure 8. Removing the Hook and Loop Strap from the Power Cable
3 Push the release tab on the power supply/cooling fan module to the right and use the handle to slide the module out of the chassis.
CAUTION: The power supply/cooling fan modules are heavy. To avoid injury, use both hands while removing the module.
Figure 9. Removing a Power Supply/Cooling Fan Module
1
Power supply/cooling fan module 2 Power socket
3 Release tab 4 Power supply/cooling fan module LED handle
5 Power switch
4 Slide the replacement power supply/cooling fan module into the chassis until it is fully seated and the release tab clicks into place.
5 Connect the power cable to the power supply/cooling fan module and make sure the cable is plugged into a power outlet.
6 Secure the power cable using the hook-and-loop strap.
7 Press the power switch on the power supply/cooling fan module to turn it on.
NOTE
: Allow several seconds for the storage system to recognize the power supply/cooling fan module and determine its
status. When the power supply/cooling fan module is functioning properly, the AC power status indicator turns green and
the power supply/cooling fan status indicator is o.
8 In Dell Storage Manager, make sure that the replacement power supply is recognized and shows as up and running.