Expanded operating temperature Specications
For temperatures between 35°C and 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours –5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C,de-rate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings maybe reported on the LCD panel and
in the System Event Log.
Expanded operating temperature restrictions
• Do not perform a cold startup below 5°C.
• The operating temperature specied is for a maximum altitude of 3050 m (10,000 ft).
• 165 W/12 core and higher wattage processor (Thermal Design Power (TDP)>165 W) are not supported.
• Six hot-swappable fans (STD fans) are required.
• Fan redundancy is not supported.
• 18 x 3.5 inch drive conguration is not supported.
• NVMe drives are not supported.
• Redundant power supply unit is required.
NOTE
: PSU failure is not supported.
• NVDIMM-Ns are not supported.
• GPUs are not supported.
• Tape backup unit is not supported.
• Non-Dell qualied peripheral cards and/or peripheral cards greater than 25 W are not supported (cooling tier =7 or above).
Particulate and gaseous contamination specications
The following table denes the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination. If
the levels of particulate or gaseous pollution exceed the specied limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
Table 27. Particulate contamination
specications
Particulate contamination Specications
Air ltration Data center air ltration as dened by ISO Class 8 per ISO 14644-1 with a
95% upper condence limit.
NOTE: The ISO Class 8 condition applies to data center
environments only. This air ltration requirement does not apply to
IT equipment designed to be used outside a data center, in
environments such as an oce or factory oor.
Technical specications 35