Steps
1. Disconnect the intrusion switch cable from the connector on the rear I/O board.
2. Using a Phillips 1 screwdriver, loosen the screw on the intrusion switch module.
3. Slide the intrusion switch module out of the slot on the system.
Figure 100. Removing the intrusion switch module
Next steps
1. Replace the intrusion switch module.
Installing the intrusion switch module
Prerequisites
1. Follow the safety guidelines listed in the Safety instructions.
2. Follow the procedure listed in Before working inside your system.
3. Remove the cooling fan cage assembly.
4. Remove the air shroud.
5. Observe and disconnect the cables from the connectors on the power distribution board.
6. Remove the PSU cage.
NOTE:
Ensure that you note the routing of the cable as you remove it from the system board. Route the cable properly
when you replace it to prevent the cable from being pinched or crimped.
Steps
1. Align and slide the intrusion switch module into the slot in the system until firmly seated.
2. Using a Phillips 1 screwdriver, tighten the screw on the intrusion switch module.
3. Connect the intrusion switch cable to the connector on the rear I/O board.