Fans
The Z9100–ON comes from the factory with two PSUs and ve fan modules installed in the chassis. The fan modules and the power
supplies, which have integrated fans, are hot-swappable.
In addition to the power supply modules, you can order and install fan modules separately.
The Z9100-ON supports two airow direction options. Do not mix airow types in a chassis; you can use only a single airow direction in a
chassis. All fans and PSUs in a conguration must be in the same airow direction.
• Normal—airow is from the I/O panel to the PSU.
• Reversed—airow is from the PSU to the I/O panel.
Environmental factors can decrease the amount of time required between fan replacements. Check the environmental factors regularly. An
increase in temperature and particulate matter in the air might aect performance; for example, new equipment installation.
CAUTION: Check the fans at six-month intervals and replace them as necessary. Regularly monitor the speeds of the fans to
accurately determine replacement intervals.
Topics:
• Components
• Fan module installation
• Fan module replacement
• Fan air lter replacement
• After Z9100–ON installation
Components
The following are the Z9100–ON fan components:
• Z9100–ON Fan module
• Z9100–ON Fan module—Reverse ow
Figure 20. Z9100–ON fan modules
7
Fans 31