EasyManua.ls Logo

Delta Electronics MCS-1800 - Page 7

Delta Electronics MCS-1800
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DELTA MCS-1800 3U Power Shelf
Installation, Operations and
Maintenance Manual
2-2
Environmental Data
System Environmental Data
Specification Value
Operating temperature
0 to +50
Storage temperature
-40 to +70
Humidity 0% to 95% RH
Altitude -300 ft. to 10,000 ft.
Weight Approximately 48 lbs.
EMI/FRI FCC Part 15, Class B and CISPR 22, Class B
Lightning/surge ANSI/IEEE C62.41-1, and IEC 1000-4-5
Seismic Bellcore GR-63-CORE, Zone 4
Safety CUL and UL Listed and Marked
2.3.2 +24V Standard Power Shelf Configuration(MODUL NAME: ES24/200-JAAxx)
(1) AC Input: 175VAC ~ 275VAC, 48Amps. Max
(2) System Capacity: 200Amps. Max.
(3) Rectifier: +24V/50A×1~4
(4) Control and Supervisory
Figure 1 shows a front view of shelf.
Environmental Data
System Environmental Data
Specification Value
Operating temperature
0 to +50
Storage temperature
-40 to +70
Humidity 0% to 95% RH
Altitude -300 ft. to 10,000 ft.
Weight Approximately 48 lbs.
Lightning/surge ANSI/IEEE C62.41-1, and IEC 1000-4-5
Seismic Bellcore GR-63-CORE, Zone 4
Safety CUL and UL Listed and Marked
2.3.3 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JBAxx)
(1) AC Input: 175VAC ~ 275VAC, 36Amps. Max
(2) System Capacity: 90Amps. Max.
(3) Rectifier: -48V/30A×1~3
(4) Control and Supervisory
(5) Load Distribution: 30A Breaker×5 @ Single Pole
(6) Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side
(7) Battery Breaker: 100A×1
(8) AC Breaker

Related product manuals