AH500 Hardware and Operation Manual
12-20
Error
Description Solution
16#E286
The network module IP of the control
mode CPU on the main backplane slot 6
cannot be detected.
1. Make sure the network cables of the network
modules on the main backplane slot 6 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module’s network cable of the
control mode CPU on the main backplane slot 6
is connected to the network port 1, the network
module’s network cable of the standby mode
CPU on the main backplane slot 6 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 6 are on the same physical
16#E287
The network module IP of the control
mode CPU on the main backplane slot 7
cannot be detected.
1. Make sure the network cables of the network
modules on the main backplane slot 7 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module’s network cable of the
control mode CPU on the main backplane slot 7
is connected to the network port 1, the network
module’s network cable of the standby mode
CPU on the main backplane slot 7 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 7 are on the same physical
16#E288
The network module IP of the control
mode CPU on the main backplane slot 8
cannot be detected.
1. Make sure the network cables of the network
modules on the main backplane slot 8 are
well-connected both on the control mode CPU
and standby mode CPU.
2. If the network module’s network cable of the
control mode CPU on the main backplane slot 8
is connected to the network port 1, the network
module’s network cable of the standby mode
CPU on the main backplane slot 8 must be
connected to the network port 1 as well.
3. Mare sure the network modules of the control
mode CPU and the standby mode CPU on the
main backplane slot 8 are on the same physical