Follow the steps below to strip the wires before assembling the AC plug:
• Strip the outer jacket from the cable for 70mm.
• Strip 22 ± 2mm of insulation from all wires ends.
Conductor cross-section:
Cu: 13.3 mm² ~ 25 mm²
(6 AWG ~ 4 AWG)
Al: 25 mm² (4 AWG)
70 mm (MAX)
22±2 mm
PE
N
L1
L2
L3
Figure 3-8 : Strip the wires
Outer Jacket
W
C
D
F
B
L
End sleeve is not able to be installed if 25mm²(4AWG) is applied.
16mm²(6AWG) dimensions of the recommended sleeve are indicated below.
WIRE SIZE
DIMENSIONS(mm)
L F
ΦC ΦD ΦW
28 18
B
10 5.8 6.2 8.7
16mm²
6AWG
- Make sure to choose proper size for AC cable.
- Failed to follow these instructions may cause AC plug damage.
- If there is any conflict between installation instruction and electrical code,
please follow the electrical code.
CAUTION!Machine and equipment damage may occur.
24
Installation