Chapter 5 Main Circuit TerminalsME300
Frame C
Figure 5-10
If you install at Ta 50°C above environment, use copper wires that have a
voltage rating of 600V and
are temperature resistant to 90°C or above.
If you install at Ta 50°C environment, use copper wires that have a voltage rating of 600V and are
temperature resistant to 75°C or 90°C.
To be UL installation compliant, you must use copper wires when installing.
on a temperature resistance of 75°C, in accordance with UL requirements and recommendations.
Do not reduce the wire gauge when using high-temperature resistant wires.
Models
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
Terminals
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4
20 Kg-cm
[17.4 lb-in.]
[1.96 Nm]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
M4
20 Kg-cm
[17.4 lb-in.]
[1.96 Nm]
6 mm
2
[10 AWG]
6 mm
2
[10 AWG]
6 mm
2
[10 AWG]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
10 mm
2
[8 AWG]
2.5 mm
2
[14 AWG]
2.5 mm
2
[14 AWG]
2.5 mm
2
[14 AWG]
4 mm
2
[12 AWG]
4 mm
2
[12 AWG]
4 mm
2
[12 AWG]
Table 5-5