Chapter 16 PLC Function ApplicationsMH300
16-69
API
ZRST
D1
D2
Clear range
40
P
bit device
Word device
16-bit command (5 STEP)
ZRST
Continuous
execution type
ZRSTP
Pulse
execution type
32-bit command
Flag signal: none
X
Y
M
K
H
KnX
KnY
KnM
T
C
D
D1
D2
Notes on operand usage:
Number of operand D
1
operand number of operand D
2.
Operands D
1
, D
2
must designate the same type of device. Refer to
the function specifications table for each device in series for the
scope of device usage.
D1: Clear ranges initial device. D2: Clear range's final device.
When the number of operand D1 > number of operand D2
, only the operand
designated by D2 is cleared.
When X0 is ON, clears auxiliary relays M300M399, changes them to OFF.
When X1 is ON, 16-bit clears counters C0
C127 (writes 0, and clears and
changes contact and coil to OFF).
When X10 is ON, clears timer T0T127 (writes 0, and clears and changes contact
and coil to OFF).
When X3 is ON, clears the data in data registers D0D100 (sets to 0).
ZRST M300 M399
ZRST C0 C127
ZRST T0 T127
ZRST D0 D100
X0
X1
X10
X3
Devices such as bit device Y, M and word device T, C, D can independently use
the clear command (RST).
RST M0
X0
RST T0
RST Y0