Interface & Communication
4 x Input, 3 x Output relays, 1 x REPO
Local EPO button & remote control
Safety: IEC/EN 62477-1,
Grid Code: AS/NZS 4777.2,
EMC: IEC/EN 61000-6-2,
IEC/EN 61000-6-4 (class A)
Applicable Battery Chemistry
Lithium-ion, lead-acid battery, flow battery
1) Output power will be de-rating if DC voltage is higher than 1250V.
2) The minimum DC voltage should be larger than 750V if the load is 100% unbalanced load.
3) Transformer or motor load or rectifier load, which has a large inrush current (Ipk>240A) is not
included.
*Specifications are subject to change without prior notice.
Table 19: Icc declaration (r.m.s. value, Icp,mr, device)
Rated current: 250A; rated voltage:500V;
Interrupt rating: 200kA.
PV312-2XL-
T250A1500V
SINOFUSE
Rated current: 250A; rated voltage:1500V;
breaking capacity: 50kA.