Installation Manual
47
Appendix
IP Degree
IP55
Interface & Communication
Digital I/O
4 x Input, 3 x Output relays, 1 x REPO
User Interface
LED, EPO
Emergency Stop
Local EPO button & remote control
Communication
Ethernet/ Modbus TCP
System Characteristic
Peak Efficiency
98%
Standby Loss
<25W @ sleep mode
Dimensions (W x D x H)
600mm x 500 mm x 2000mm
Net Weight
<250 kg
Standard Compliance
Certificate
Safety: IEC/EN 62477-1,
Grid Code: AS/NZS 4777.2,
EMC: IEC/EN 61000-6-2,
IEC/EN 61000-6-4 (class A)
Product Conformity
RCM
Applicable Battery Chemistry
Lithium-ion, lead-acid battery, flow battery
1) Output power will be de-rating if DC voltage is higher than 1250V.
2) The minimum DC voltage should be larger than 750V if the load is 100% unbalanced load.
3) Transformer or motor load or rectifier load, which has a large inrush current (Ipk>240A) is not
included.
*Specifications are subject to change without prior notice.
Table 19: Icc declaration (r.m.s. value, Icp,mr, device)
Characteristics of SCPD
Ports
Icc
Icp,mr
Type
Location
Specification
AC
10kA
5kA
L50QS250.V,
LITTELFUSE
FU1, FU2,
FU3
Rated current: 250A; rated voltage:500V;
Interrupt rating: 200kA.
DC
20kA
5kA
PV312-2XL-
T250A1500V
SINOFUSE
FU4,FU5
Rated current: 250A; rated voltage:1500V;
breaking capacity: 50kA.