OPERATION MANUAL FOR PCS100HV
69
7. Miscellaneous
7.1. System Time Setting [WHEN NEED]
Table 47 system time configuration
ADDR
(HEX)
ADDR
(DEC)
TYPE
DEFINITION
DESCRIPTION
Unit
RW
Min
Max
Default
OA
100D
4109
Uint16
EN_CMD_TIME_YEAR_MONTH_SET
Uint8(MSB): Local Time: Year to
be set. Range: 0-99, for example
2021Y21
Uint8(LSB): Local Time: Month to
be set
NA
RW
0
23502
1
No
100E
4110
Uint16
EN_CMD_TIME_DAY_HOUR_SET
Uint8(MSB) Local Time: Day to be
set
Uint8(LSB) Local Time: Hour to be
set
NA
RW
0
7960
256
No
100F
4111
Uint16
EN_CMD_TIME_MIN_SEC_SET
Uint8(MSB) Local Time: Minute to
be set
Uint8(LSB) Local Time: Second to
be set
NA
RW
0
15420
0
No
For example: 01:09:30 01/12/2018
Table 48 Set system time.
STEP
CMD
DESCRIPTION
REMARK
Option