Chapter 11 Description of Parameter Settings|C200 Series
11-36
Settings Functions Descriptions
Multi-function Output
MO =d47
Output Frequenc
y
02-32
RUN
RUN
Ti me
Output Frequency
< Pr.02-34
48~49 Reserved
50
Output for CANopen
control
For CANopen communication output
51 Output for RS-485 For RS-485 output
Example: Crane Application
02-32
02-32
Output
Frequency
Freq. Command>02-34
& output current >02-33
Freq. command<02-34
or output current <02-33
multi-function output
MO=42 (Active when
Fcom>=02-34, output
current>02-33 and time
>02-32)
It is recommended to be used with Dwell function as shown in the following:
Multi-function output
MO= 42
( Activate when
Fcmd >= 02-34
output current > 02-33
Time > 02-32)
07-16 Dwell
Freq.
at Accel.
07-15
Dwell Time at Accel.
Output Freq.
02-32
Brake Delay Time
Set 07-16=02-34and
output current >02-33
07-17
Dwell Time atDecel.
Set 07-18=02-34 and
output current <02-33
07-18 Dwell Freq.
at Decel.
02-32
Brake Delay Time
Reserved
Multi-function Output Direction
Factory Setting: 0000h