Chapter 2 Installation and Wiring_VFD-B Series
2-30
Revision 10/2005, BE13, SW V4.08
20 HP to 30 HP (15kW to 22kW)
VFD150B23A/43A/53A, VFD185B23A/43A/53A, VFD220B23A/43A/53A
3
IM
POWER
S/L2
R/L1
- ( ) ( )
+ DC DC
T/L3
+1
-
+2
MOTOR
W/T3V/T2
Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG (3.3-0.2 mm
2
)
Power Terminal
Torque: 30Kgf-cm (26 in-lbf)
Wire: 2-8 AWG (33.6-8.4 mm
2
)
Wire Type: Stranded Copper only, 75qC
NOTE
To connect 6 AWG (13.3 mm
2
) wires, use Recognized Ring Terminals