EasyManua.ls Logo

Delta VFD037CB43A-20 - Page 240

Delta VFD037CB43A-20
363 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 11 Description of Parameter Settings|C200 Series
11-141
Settings 1~40Hz (IM)/ 1~100Hz (PM)
After estimating inertia and set Pr.11-00 to bit 0=1 (auto tuning), user can adjust parameters
Pr.11-03, 11-04 and 11-05 separately by speed response. The larger number you set, the faster
response you will get. Pr.11-02 is the switch frequency for low-speed/high-speed bandwidth.
ASR (Auto Speed Regulation) control (P) 1
Factory Setting: 10
Settings 0~40 Hz (IM)/ 1~100Hz (PM)
ASR (Auto Speed Regulation) control (I) 1
Factory Setting: 0.100
Settings 0.000~10.000 sec
ASR (Auto Speed Regulation) control (PI) 2
Factory Setting: 10
Settings 0~40 Hz (IM)/ 0~100Hz (PM)
ASR (Auto Speed Regulation) control (I) 2
Factory Setting: 0.100
Settings 0.000~10.000 sec
ASR(Auto Speed Regulation) Control (P) of Zero Speed
Factory Setting: 10
Settings 0~40 Hz (IM)/ 0~100Hz (PM)
ASR(Auto Speed Regulation) Control (I) of Zero Speed
Factory Setting: 0.100
Settings 0.000~10.000 sec
Gain for ASR Speed Feed Forward
Factory Setting: 0
Settings 0~100%
This parameter is used to improve speed response.
ASR
11- 14
00-20
+
+
+
11- 1 7~11- 20
-
+
Tq Bias
Speed feedback
Torque limit
Torque
command
11- 12
Gain for ASR
speed feed forward
PDFF Gain Value
Factory Setting: 30
Settings 0~200%
After finishing estimating and set Pr.11-00 to bit 0=1 (auto tuning), using Pr.11-13 to reduce