Chapter 4 Operation InterfaceVP3000
157
CMC-EC01
Lights
Definition
Description
NET1
(Link/
Active 1)
Communication
connection and
action indication
Green
light
ON: Network connection is normal
OFF: no network connection
Blinking: Network in operation
NET2
(Link/
Active 2)
Communication
connection and
action indication
Green
light
ON: Network connection is normal
OFF: no network connection
Blinking: Network in operation
NET3
(RUN)
Communication
connection status
indication (OUT
LINK)
Green
light
ON: communication is in operation
OFF: initial status (INIT)
Blinking: pre-operating status or starting status
NErr
Fault Indication
Red light
ON: serious communication error or controller
error
Blinking: start error (Checksum error), basic
configuration error
Single flash: status switching error
Double flash: communication timed-out
CMC-COP01
Lights
Definition
Description
NET1
(ERR)
Fault Indication
Red light
ON: Bus OFF
Single flash: at least one CANopen packet failure
Double flash: Guarding fail or heartbeat fail
Triple flash: SYNC failure
NET2
(RUN)
Communication
connection status
indication
Green
light
ON: CANopen is in operation
OFF: CANopen is in initial status
Blinking: CANopen is in pre-operation status
Single flash: CANopen is in stop status