Chapter 3 Electrical WiringVP3000
89
Frame K
Figure 3-29
If you install at Ta 50°C environment, use coper wires that have a voltage rating of 600V and are
temperature resistance to 75°C or 90°C.
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of 600V
and are temperature resistance to 90°C or above.
To be UL installation resistance of 75°C, in accordacne with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire.
Model
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3
Terminal
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec.
and Torque
(±10%))
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec.
and Torque
(±10%))
VFD460VP43AFTCA
240 mm
2
*2
(400 MCM*2)
185 mm
2
*2
(350 MCM*2)
M10
153 kg-cm
(132.8 lb-in.)
(15.00 Nm)
240 mm
2
(400 MCM)
185 mm
2
(350 MCM)
M10
153 kg-cm
(132.8 lb-in.)
(15.00 Nm)
VFD485VP43AFTCA
185 mm
2
*2
(350 MCM*2)
240 mm
2
(400 MCM)
185 mm
2
(350 MCM)
VFD460VP43BFTCA
185 mm
2
*2
(350 MCM*2)
240 mm
2
(400 MCM)
185 mm
2
(350 MCM)
VFD485VP43BFTCA
185 mm
2
*2
(350 MCM*2)
240 mm
2
(400 MCM)
185 mm
2
(350 MCM)
VFD460VP43BSTCA
185 mm
2
*2
(350 MCM*2)
240 mm
2
(400 MCM)
185 mm
2
(350 MCM)
VFD485VP43BSTCA
185 mm
2
*2
(350 MCM*2)
240 mm
2
(400 MCM)
185 mm
2
(350 MCM)
Table 3-23