This section provides a list of the more frequently encountered malfunctions, their causes and corrective actions. The operator or maintenance
personnel can perform some corrective actions, and others may require the assistance of a qualified D
eWALT technician or your dealer.
Problem Code
Engine will not start (See engine instruction manual for more information) .............................................................................................1,2,3,4
No electrical output .................................................................................................................................................................................5,6,7,8,9,18
NOTE: Ifthereisstillnopoweratthereceptacles,takethegeneratortoanauthorizedD
EWALT service center. To locate a DEWALT service center
nearest to you, call 1-800-4-D
EWALT (1-800-433-9258)
Repeated circuit breaker tripping ......................................................................................................................................................................10,11
Generator overheating ......................................................................................................................................................................................10,12
No auto idle ........................................................................................................................................................................................13,14,15,16,17
CODE POSSIBLE CAUSE POSSIBLE SOLUTION
1 Engine switch in OFF position. Turn to ON position
2 Choke in wrong position Adjust choke accordingly
3 Fuel shut-off valve in closed position Open fuel shut-off valve
4 Unit loaded during start-up Remove load from unit
5 Faulty receptacle Contact a D
e
WALT factory service center or a D
e
WALTauthorized
service center
6 Receptacle thermal circuit breaker tripped Depress and reset