Control Board Error 82
Condition Model jumper not Selected or detected. Relay Board or control board.
Control
Action
Error will display and cycle will stop.
Exit The machine will not start and the Error Code will continue to be displayed until
the condition no longer exists and the prompt is followed to Reset the Error Code
and return the Machine to Idle Mode.
Customer
Action
Inspect Model Jumper on Relay board (P3) make sure connected and present.
Inspect I2C harness between control (Relay Exp.)and relay board (P1). Inspect for
12VO_SW LED make sure iluminated. If not test 12Vdc power supply, (must be
11.4 or above). Inspect harnesses if pinched of damaged (loading door and lint
switch).