“Signalisation” Menu
----->>>>> ----->>>>>
OR
----->>>>> ----->>>>>
Floor 0 - 12:30:56
< Signals >
Parameter Description Navigation Values
Default
Value
Select door
B at floor
Configuration of door A for each floor: set access
to each floor and open or close door parking at
floor (for automatic doors)
◄► (Selection)
▲▼ (Change floor)
No;
Pkg. Door
close;
Pkg. Door
open
Pkg. Door
close
Door B
Open/Close
time
Door B without limit switch: door opening/closing
time
▲▼
(Increase/Decrease)
1 s <-> 60 s 10 s
Door B
start delay
Door B manual: time before start
▲▼
(Increase/Decrease)
0,1 s <-> 9,9
s
2,0 s
Slipping
Door B
Door B with limit switch: time before slipping fault
▲▼
(Increase/Decrease)
1 s <-> 60 s 10 s
Door B
powered
Door B powered during the run. Not considered
for manual or independent doors
◄► (Selection)
No
Yes
Yes AT40
No
Advanced
opening
Parameter for door advanced opening (opening
starts before car stop).
◄► (Selection)
No;
Yes
No
Photocell
Type
Parameter to select the type of photocell:
NO photocell: contact opens if the beam is free.
The contact closes if the beam is interrupted. The
shock, photocell and open door contacts must be
wired in parallel.
NC photocell: opposite of the NO photocell. The
shock, photocell and open door contacts must be
wired in series.
NOTE: The shock, photocell and open door
contacts must all be of the same kind (NO or NC)
◄► (Selection)
NO;
NC
No
Table of Parameters:
Parameter Description Navigation Values
Default
Value
Table of Parameters