Parameter Description Navigation Values
Default
Value
Temperature
sensor
during
operation
Indicates whether the car can be blocked by the
motor temperature sensor also during travel
◄► (Selection)
No;
Yes
No
Anti-
nuisance
fault
Parameter for the detection of the anti-nuisance
fault (number of stops without photocell activation
after which all car calls are cancelled)
◄► (Selection)
▲▼ (No calls)
No; Yes
2 <-> 10
No
3
Out of
service floor
Floor for out of service.
Parking floor when HS input is enabled.
▲▼
(Increase/Decrease)
0 <-> Floor
No.:
0
Automatic
return
Parameters for elevator car automatic return at
floor: Return floor and Minimum waiting time
before automatic return
◄► (Select
parameter)
▲▼ (Change value)
No
0 <-> Floor
No.:
1 min <->
60 min
No
0
15 min.
Return
zones
Advanced settings for return at floor at planned
hours / days:
-) Day (0 = everyday, 1 = monday … 7 = sunday);
-) Selected time interval (4 interval each day);
-) Return floor;
-) Start time;
-) End time (max time: 7h 45 min);
◄► (Select
parameter)
▲▼ (Change value)
R. zone
timing
Timing for selected return zones
◄► (Selection)
▲▼ (Change value)
No; Yes
1 s <-> 120
s
No
60 s
Call erasing
at floor
Erasing all calls at floor where the elevator car
stops, with no control of the direction (only for full
collective installations)
◄► (Selection)
No;
Yes
No
Drift control
(FR)
Drift control (France) ◄► (Selection)
None;
Traction
drive;
Drum
machine
None